top of page
Room Controller
Fancoil thermostat in high-quality design for individual single-room temperature- and fan control. A glass surface with intuitive touch control buttons and display combine design, feel and functionality in an outstanding way. The internal controller of the JOY calculates control values for fans and heating/cooling applications, which are provided via analog or digital outputs (depending on type). The possible integration of various external sensors (e.g. window contacts, change-over, condensation sensors, etc.) allows temperature and fan control tailored to the application. The device can be mounted in a standard flush-mounted box.
Technical Data
Application/type | Fan coil thermostat, Room thermostat |
Purpose | Room Climate Control, Measure values |
Measured values | temperature, relative humidity |
Interface | EnOcean (868 MHz), RS485 Modbus, RS485 BACnet, Active, 0..10 V, Switch contact |
Functions | hardware outputs, fan control relay, fan control 0..10 V, heating + cooling relay, heating + cooling 0..10 V, to control 6-way control valve, to control valve actuators SAB, Fan coil thermostat, change-over, integrated PI controller, integrated PI and two-position controller, integrated PI and two-/three-position controller, frost protection, window/door monitoring, presence, MSG-server for 2nd zone |
Operating functions | setpoint adjustment temperature, fan stage adjustment, standby/presence detection |
Operating elements | 5 touch buttons |
Configuration | uConfig, BUS |
Output voltage | 0..10 V, 3x 0..10 V, max. load 5 mA, to control EC fan, heating + cooling, heating + cooling or to control 6-way control valve |
Output switch contact | 2x contact NO, 1x heating, 1x cooling, load max. 500 mA (240 V, Triac), 3x contact NO, fan stages, load max. 3 A |
Input | 1x input for NTC10k or floating contact, 1x input for potential contact (230 V ~), 1x input for floating contact, 2x input for floating contact |
Network technology | RS485 Modbus, RS485 BACnet (MS/TP) |
Radio technology | EnOcean (IEC 14543-3-10) 868 MHz, transmission power <10 mW |
Data transmission | 20 channels for sender, receiver or message-server, RTU, half-duplex, baud rate 9.600, 19.200, 38.400 or 57.600, parity: none (2 stop bits), even or odd (1 stop bit) |
Operating range temperature (°C) | 0..+50 |
Output signal temperature | scaling according EEP, 0..+40 °C, 0..+50 °C |
Operating range humidity | max. 85% rH non-condensing |
Accuracy temperature | ±1 K (typ. at 21 °C), within default measuring range |
Measuring range humidity | 0..100% rH non-condensing |
Accuracy humidity | ±2% between 10..90% rH (typ. at 21 °C) |
Power supply | 24 V = (±10%) SELV, 24 V ~ (±10%) SELV, 85..260 V ~ |
Power consumption | typ. 2,5 W (24 V =), max. 2,5 VA (260 V ~), max. 3 VA (260 V ~) |
Display | LCD 60x44 mm, 240x160 px, backlight cold white |
Enclosure | PC, cover glass |
Colour | pure white, black |
Protection (IP) | IP30, according to EN 60529 |
Connection | terminal block, max. 1,5 mm², inputs max. 1,0 mm² |
Mounting | in standard EU box (Ø=60 mm, depth min. 45 mm) |
Packaging length (mm) | 196 |
Packaging width (mm) | 162 |
Packaging height (mm) | 37 |
Device length (mm) | 140 |
Device width (mm) | 78 |
Device height (mm) | 35 |
Weight (g) | 195 |
bottom of page